DESIGN

MS 230 is a compact unit for installation in el-motor starter cabinet.
 
 
-

A motor can be remote controlled via MS230 (See connection diagram). A remote unit cannot operate if the local MS 230 is at LOCAL MODE. However the status of all indicators are shown on the remote unit.
 

 
OPERATION / FUNCTIONS
 
 
-

Select the operation modus, either LOCAL or REMOTE
 
 
-

Press the START button MS230 will activate the main contactor (K1). Auxiliary contact feedback from K1 will indicate that the motor is running
 
 
-

To stop the motor press the STOP/RESET button
 
 
-

The motor will trip by any of the following signals:
Motor protection, earth fault and emergency stop. Reset trip by pressing the STOP/RESET button
 
 
-

Pressing the HEATER ON button activates the motor standstill heater. The standstill heater will be automatically switched off when the motor is restarted
 
 
-

Trip cased motor to stop can be reset by pressing the STOP/RESET button
 

 
SAFETY

MS 230 is fitted with various protection devices against incorrect electrical connection and electric disturbance.
CE tested according to EN 50 082-1; EN50 081-1
 

 
INSTALLATION

MS230 is delivered with pre-wired and marked cables, length 1,0m. Connection of 7 to 12 wires in one end is what is needed to complete an el-motor control circuit.
MS 230 fits all sizes of el-motors. It can also be used with, for example, an el-motor soft drive.
 

 


INPUT/OUTPUT SIGNAL

See MS230 Connection diagram  
 

 
TECHNICAL DATA

Power supply: 230VDC 50/60Hz; max 20mA
Output to K1: Volt free max 230VAC10A
Out put to K3: Powered from MS230 max. 35mA12VDC
Inputs: Powered from MS230 12VDC
Protection: Front IP55. Rear IP20
Wires: Standard length 1.5m
Environment: -5 to +60°C Max 90% noncondensing
Dimension: 48x96x85mm (HxWxD)
Cut out: 48x92mm (HxW)